INFORMATION SHEET

 

AIR LOCK SYSTEM

Information Sheet Number 62S-106

 

INTRODUCTION

 

            When automatic boiler controls are installed, the normal steaming configuration for the automatic systems is in automatic.  Unfortunately, from time to time errors occur in the plant that limit the ability to keep the systems in automatic, such as a loss of control air casualty.  An airlock system is installed on automatic boiler control systems to lock the last known air signal to the final control elements.  This provides time for the operator to gain local manual control.  The minimum time required for this system to hold is 10 minutes with no more than a 10 percent pressure drop in accordance with the PMS card that requires system testing.

 

REFERENCES

 

            (a)  Automatic Combustion and Feedwater Control Systems NAVSEA 0951‑036‑9010

            (b)  Steam Plant Controls NSTM Chapter 225

            (c)  Boiler Technician 3 and 2  NAVEDTRA 10535 G, Chapter 6

            (d)  Boiler Technician 1 and C NAVEDTRA 10536 F, Chapter 8

            (e)  Main Boilers, NAVSEA 0951-LP-022-6010

 

INFORMATION


 

A.                 Components (Figure 1)

 

1.  Pressure regulating valves maintain 80 psig to the airlock system from control air supply pressure.  Pressure from the valve is piped to the master trip valve and passed to the individual trip valves when the master valve is open.

 

2.   Control panel panel contains two 0-200 psig range pressure gauges and a reset valve with   a push button.  A pressure switch set at 75 psig is connected to an indicating light panel     and a buzzer.  The light panel contains a transformer, a white light bulb to indicate the      airlock panel is energized, and a red light bulb to warn of impeding loss of control air pressure.  A rotary switch enables the operator to silence (cutout) the buzzer signal once the alarm has been sounded.

                                                                    Figure 1

 

 

3.  Master trip valve is a switching valve manufactured by Fisher Control Co.  The unit contains a diaphragm, three 1/2 inch ports, and a steel spring set a t 65 psig.  There is only one master trip valve in the system.  The valve is connected to all the individual trip valves at each final control element.  The valve is held in the open position by control air pressure and is calibrated to close when the air pressure drops to 65 psig.

 

4.  Individual trip valves are  Fisher 3-way switching valves (individual trip valve) installed at each final control element located in the main machinery space.  The valves are identical in construction to the master trip valve.  The spring however, is set for 40 psig.  These valves are held open by 80 psig pressure provided from the airlock regulator through the master airlock and are calibrated to close when the airlock system pressure drops to 40 psig.  Individual airlocks are installed on the fuel oil control valves, forced draft blower steam admission valves, main feed pumps (if automatic controls are installed) , and feedwater control valves.

 

5.  Three-way vent valves (one for each individual trip valve) are installed between the individual trip valve and the actuators of the final control devices.  The valve allows the operator to release or vent the control air trapped between the individual trip valve and the final control element when shifting the final control element to local manual control.  Venting the signal allows for full range of motion from minimum to maximum position of the final control element.

 

6.  Reset buttons are used to reset the air lock system.  When the valve is depressed, control air rushes up under the diaphragm in the master trip valve, thus opening it and allows air to pass to all individual trip valves in the system, opening them.

 

B.         System operation

 

1.  As air pressure drops from 125 psig:

 

a.  115 psig high start/stop compressor starts

 

b.  110 psig low start/stop compressor starts

 

c.  85 psig priority valve closes ensuring all air is sent to vital air systems

                       

d.  80 psig alarm sounds in the engine operating station (EOOW)

 

e.  75 psig alarm sounds in the fireroom

 

f.  65 psig the master trip valve closes aligning air from all the individual trip valves to the atmosphere.  When the airlock system pressure drops to 40 psig all the individual valves will close, thus locking in the last signal to the final control element.