INFORMATION
SHEET
AUTOMATIC
BOILER CONTROL SYSTEMS
Information
Sheet Number 62P-113
INTRODUCTION
Automatic
Boiler Controls (ABCs) are used extensively on modern surface ships to control
the operation of the boiler and it's auxiliaries under all load conditions from
minimum to 120%. The ABCs include the various sub-systems necessary in
maintaining both combustion rate and sufficient feedwater supply to answer all
steaming requirements within allowable tolerances. This study guide will
present theory followed by sub-systems and finally system integration.
REFERENCES:
(a) Principles of Naval Engineering NAVPERS 10788 B
(b) Boiler Technician 3 and 2 NAVEDTRA 10535 G, Chapter 6
(c) Automatic Combustion and Feedwater Control
System, NSTM 225
(d) Introduction to Naval Engineering (Second
Edition)
INFORMATION
A. The automatic boiler control system
(ABC) viewed in its entirety, can be likened to that of a computer.
Unlike the electronic marvels we've grown so accustomed to, this system utilizes pneumatic signals
(pressures) to process its information and effect
the necessary changes to the
various engineering plant components.
ABC is an all inclusive term
for a system which is comprised of the following four subsystems: automatic combustion
control (ACC), feedwater control
(FWC), feed pump control (FPC) , and
air lock control
(ALC). Control systems such as these
are referred to as closed loop systems. A
true closed loop system is self correcting in that it makes all corrective
changes in direct response to its
continuously monitored feedback signal.
An automatic control system, regardless
of its application, must meet the
following criteria:
1.
Measure
2.
Compare
3.
Compute
4.
Correct
B. Terminology: As in any given trade or specialty, specific
names/terms are assigned to various
items, processes, or occurrences associated with it. In order to better understand the workings of these systems,
a select few of these terms gleaned from Reference
C are provided.
1. Actuating Signal: The pneumatic pressure (signal) sent from a
relay or controller which works upon
the bellows or diaphragm within an actuator.
2. Actuator: That component of a final control element
that converts the actuating signal into a mechanical position change in order
to change the operating point of the final control element.
3. Bias: A means of manually altering the actuating signal by either
adding to or subtracting signal pressure prior to the positioner or actuator
while the system is in the automatic mode of operation.
4. Boiler
Load: The rate of steam generation
of the boiler at set point at any instant.
5. Boiler
Master: A boiler's Automatic/Manual
(A/M) control station located on the boiler control console.
6. Closed Loop: A signal path that includes a forward path,
a feedback path, and an error detector so arranged as to form a closed circuit.
7. Console: The boiler control panel that provides an
operator with a remote manual means of controlling the system. The console also gives a visual indication of system performance during automatic
operation.
8. Controlled
Variable: That quantity or
condition which is measured and controlled
such as:
a..
Steam pressure
b. Water
pressure
c. Fuel
pressure
d. Air
flow
9. Cycling: Control
system instability which causes a continuous even variation of a
systems set point.
10. Feedback: The returning of a fraction of a controlled variable output
signal to the input of a systems
controller input.
11. Hunting: Control system instability which causes a continuous erratic cycling around a systems set point.
12. Master Demand Signal: The input signal to both the air and fuel
flow loops in the ACC system.
13. Open Loop System: A system in which the output is allowed to
vary according to the characteristics of the system and of the input signal
without reference to the system output (possess no feedback loop).
14. Setpoint: A reference force (generally spring tension) in a systems
controller that represents a desired output (i.e. steam drum pressure, feed
water header pressure).
15. Shrink: A "false" and temporary drop in steam drum water level
caused by a down power maneuver (i.e. closing
down on the main engine throttle/s).
Because the boiler's ABC system can
not anticipate a decrease in demand before it happens, a back pressure
greater than boiler setpoint is created.
At this point in time, this excess pressure exerts a force upon the
water in the steam drum causing the steam bubbles within the entire boiler to
compress. This in turn causes the volume of the water to momentarily
decrease until the boiler's firing rate has adjusted itself to the new
demand. As soon as the boilers heat
balance has been corrected, water level will begin to return to normal.
16. Swell: This is the opposite occurrence of shrink and results from an
up-power maneuver. Again, because an
ABC system can not anticipate a
change in boiler load (increase or decrease), steam drum pressure will drop in
direct proportion to the increased amount of
steam that is being admitted to the main engine/s turbines.As the
pressure in the steam drum decreases the steam bubbles within the boiler are
able to expand causing a "false" rise in water level. As the ABC system begins to respond to the
new demand (i.e. an increase of both combustion rate and feed flow), the drum
level will return to normal.
C.
Subsystems:
1. Automatic Combustion Control system
(ACC): The job of the ACC system is
simply to maintain the proper amount of fuel and air necessary to maintain
steam drum/superheater pressure at setpoint.
a. The
ACC system is comprised of three loops:
(1) Steam Loop (supervisory)
(2) Air Loop (Forced Draft Blowers)
(3) Fuel Loop
b. Depending upon a particular ships
engineering plant configuration, steam pressure setpoint may be measured from one of three possible locations:
(1) Steam Drum
(2) Superheater outlet
(3) A common header between boiler superheater
outlets
c. Sufficient air to completely burn the fuel
admitted to the firebox is referred to as the "Air to Fuel Ratio".
The ACC system is designed to provide slightly more air (approximately 15%
more) to the amount of fuel required for any given boiler load. This provides for more efficient combustion
as well as preventing the boiler from producing black smoke.
d. Slight variations upon transient load
changes are acceptable (5%) when monitoring drum pressure. However, when steaming at steady-state
conditions, setpoint must be maintained.
2. Feedwater Control System (3 Element
Control System)
a. The Feedwater Control (FWC) System's primary
function is to maintain normal
boiler water level setpoint within plus or minus one inch at all boiler loads.
The three element feedwater control system is also designed to compensate for
the effects of "shrink" and "swell".
b. The FWC System senses system parameters via
transmitters at three different locations.
They are:
(1) Steam Flow Transmitter: Senses flow at the saturated steam line
leaving the steam drum. The signal from
this unit is termed Demand.
(2) Feed Flow Transmitter: Senses flow at a boiler's feed pipe, prior
to the economizer inlet. This is the
systems Feedback signal.
(3) Drum Level Transmitter: Senses actual boiler water level directly at
the steam drum. This is the Supervisory signal.
c. Steam flow and feed flow must match one for
one (i.e. one pound of steam out equals one pound of feed water in) in order to
maintain constant thermal / pressure equilibrium and normal water level at
steady state steaming conditions.
d. A delayed response signal from the Feed Flow
Controller to the Feedwater Control Valve is the means in which the system
compensates for shrink and swell.
3. Main Feed Pump Constant Pressure Control
System:
a. The Main Feed Pump Constant Pressure Control
System is designed to maintain a constant supply of feedwater to the boiler at
sufficient pressure (75 - 150 psig
above steam drum pressure) under all load conditions.
b. On an increase in demand, the Feedwater
Control Valve opens. When this occurs,
the resistance to flow within the feedwater piping lessens resulting in a
decrease in feed pressure. The Feed Pump Control (FPC) system senses this
decrease and speeds up the main feed pump, causing discharge pressure to return
to setpoint.
c. On a decrease in demand, just the opposite
will occur. As the Feed Water Control
valve closes, feed pressure will increase causing the system to slow the feed pump to its set point
pressure.
D. Identification of Control Systems
1. Automatic control systems are identified by
their principle manufacturer and application. Conventionally powered steam
ship's currently in commission use either Hagan
or General Regulator (GR) automatic
boiler control systems. The individual manufacturer may use a part made by
someone else much the same as Ford using Firestone tires. Barton
and Moore Corporation supply several compatible components. They may be used
interchangeably with either Hagan or General Regulator components.
2. Although Hagan has been the Fleet standard
for years, General Regulator has recently become the predominant system
installed in the majority of steam ships currently in commission.
E. Control Agent
1. Automatic boiler controls operate with
clean, dry air normally supplied from the ship's low pressure air system. This however is not the only source of air
as some ships are designed with their own dedicated air compressors for this
system. Whatever the configuration, quality and pressure are important
to the reliability of the control systems it supplies.
2. The advantages of air as a control medium
are two fold in that:
a. It withstands small leaks without hampering
the system's operation.
b. Heat and humidity have very little,or no
effect on system components.
3. The quality of the air is dependant upon the
design of "oil free" compressors and air dehydrators. Without these, the control systems will
become fouled causing such problems as obstructing tiny orifices and the
failure of rubber seals and diaphragms.
4. While the air signals may vary within the
control systems the source of supply must remain constant. This air, normally
between 115 - 125 psig, must first be reduced in pressure before it is
introduced into the system/s. For
example:
a. Hagan components operate at a pressure
range of 0 - 65 psig
b. General
Regulator systems operate on a range of
3 - 15 psig
F. Automatic Boiler Control Components
1. Transmitter (XMTTR) - These
components are of varying design and are used on all the ABC systems. As the name implies, a transmitter does
nothing more than MEASURE a variable and send out that information via a pneumatic
signal. If a transmitter were a
watchstander, it would be nothing more than a messenger, that is to say, its
function is to relay information. The
following are transmitters found in a typical ABC system:
a. Steam pressure (ACC)
b. Air flow (ACC)
c. Steam flow (FWC)
d. Feed flow (FWC)
e. Drum level (FWC)
2. The
controller is the "brain" within any system in which it
is installed. Its function is to
receive the pneumatic signal or "message" sent from its transmitter, COMPARE it to its required value, and COMPUTE the difference between what it
is presently receiving to what is required and send out a pneumatic signal that
will bring the system back to set point.
An example of this operation is as follows:
30 psig Required value (Set point)
- 23 psig Signal from Transmitter
07
psig is
added to the current controller output signal of let's say 41 psig, to make a
new output signal of 48 psig.
3. A Relay is similar to that of a
controller in that it receives one or more pneumatic signals from a component
or component and either combines, forwards or subtracts these signals to
develop either an increasing or decreasing output signal. A relay is an
intermediate component in that it will always be located between a controller
and a final control element. Examples
of these are the steam flow rate relay and fuel oil characterizing relay in the
ACC system.
4. A/M Stations (Automatic and/or Manual
control) are components which provide a means of selecting either automatic or
remote manual control of a system or one or several of its final control
elements. Despite their outward appearance
and similarity in basic design, there are two different types. A/M stations are termed either 2 way or 4
way in their function.
a. 2-Way stations provide the operator
with a means of selecting a mode of operation only. In other words; in the automatic mode, the automatic signal
passes straight through this component totally unaltered whereas in the manual mode, the automatic signal is
blocked off from passing through and the console operator generates the desired
output signal. This mode of operation
is used for different evolutions such as
boiler light-off, specific operations (i.e. surface blowing), or
troubleshooting.
b. 4-Way stations also provide the operator with the means of
selecting the mode of operation and in addition to this, a means to introduce BIAS to the automatic signal. To add or subtract bias to an automatic
signal is nothing more than "customizing" the output signal to a
particular final control element. A
four-way station is used for the parallelling of like pieces of equipment (i.e.
FDBs and boilers) much like one would parallel electric generators.
5. Signal range modifiers are used whenever a dissimilar
manufacturers component is used within a system's loop. The most common placement is that of a
Woodward Governor which is used to position a steam driven piece of machinery's
steam admission valve. Because of the
disparity in signal range pressures between components, an
"interpreter" or "translator" is required in order for
these dissimilar components to work together.
6. A positioner is the pneumatically
operated component of the final control element. It provides the positive movement for the final control element
proportional to the incoming signal.
7. The Final Control Element is a valve,
the actual "doing" part of the system. By manipulating the position of these various valves, the system
will effect the required changes to forced draft blower and main feed pump
speeds, boiler water level, and fuel oil pressure to the burner front. In short, this is the component that will CORRECT bringing its loop or system
back to setpoint.
G. Air Lock System: This system is installed to provide time
for the operators to shift the plant to
local manual control should the air supply fail. It consists of a master air
lock valve in the air supply
line to the control console and an air lock valve in the air supply line to each final control element except for the
main feed pump recirculating valve (if so installed).
1. In the event supply air fails, the air lock
valves will shut locking in the last signal to each final control element and
to the console. This keeps all final
control elements "FROZEN"
in their last position to prevent a loss of control of the boiler. PMS requires that the air lock system hold
for a minimum of ten minutes.
2. At this point the EOOW will order the
operators to shift control of the boiler to local manual control. The bridge,
upon receiving this message from the EOOW, should
not deviate course and speed as the control systems will not respond and
the securing of the engineering plant will be inevitable.
3. In the event the air lock system does not
hold, each final control element will go to a fail safe position as follows:
a. Fuel Oil Control Valve - MINIMUM
b. Feedwater Regulating Valve - OPEN
c. Forced Draft Blower Governors - MINIMUM
d. Main Feed Pump Governors - MAXIMUM
e. Main Feed Pump Automatic Recirculation Valve
(if installed) - OPEN
4. Each final control element can be operated
manually with the exception of the main feed pump automatic recirculation valve
which immediately goes to its fail position in order to protect the main feed
pump from overheating.
H. ABC MODES OF OPERATION
1. Automatic
a. In this mode, the control system will
maintain the system at the set point throughout its full range without human
intervention.
b. Bias can be introduced into a system having
a four-way A/M station while in automatic.
2. Remote Manual
a. In this mode, the control system is operated
manually at the control console or station by first shifting to the manual
position. This prevents the automatic
signal from passing through to the final control element down stream. The operator must now do the thinking and
manually generate the necessary signal to that system's final control
element/s.
b. This mode of operation is used for lighting
off and securing, during casualties, and for troubleshooting the system.
3. Local Manual. In this mode, direct manual control is taken by individual
watchstanders at the various final control elements.
a. Used when all remote means of control are
lost such as with a loss of control air.
b. Operation in this mode is very difficult as
reaction time is slowed and human error more prevalent.
I. Automatic Boiler Control System
Operation
1. Increase in Demand
a. Automatic Combustion Control System -
When the main engine throttle valve is opened, steam pressure decreases causing
the system demand signal to increase. This causes the forced draft blowers to
speed up and the fuel oil flow to increase.
Even though the forced draft blowers receive an increasing signal, the
blowers are slower to respond because of having to overcome inertia. The system will stabilize when setpoint
reached.
NOTE: A component in the automatic combustion
control system called the MINIMUM SIGNAL SELECTOR, ensures that the
system functions in a series/parallel operation. That is, air leads and fuel
follows on an increase in steam demand, and air and fuel oil decrease together
on a decrease in steam demand.
b. Feedwater Control System - Steam Flow
increases which calls for more water,
but due to swell the FWC delays this increase for more water, besides the
feedwater regulating valve will open returning the water level to normal. When
steam flow and feed flow are equal and water level is normal the system will
stabilize at the new demand.
c. Main Feed Pump Constant Pressure
Control System - Feed pressure decreases below setpoint causing the main feed
pump to increase in speed until feed pressure is reestablished at setpoint.
d. Main Feed Pump Recirculation Control
System - Assuming that the recirc valve is open; when flow through the main
feed pump increases to 90 GPM, the recirc valve will shut as there is
sufficient flow through the main feed pump to prevent it from overheating.
2. Decrease in Demand
a. Automatic Combustion Control System -
When the throttle valve is shut, steam pressure increases causing the system
demand signal to decrease. This causes the forced draft blowers to slow down
and the fuel oil flow to decrease. The system will stabilize when setpoint is
reached.
b. Feedwater Control System - Steam flow
decreases which calls for less water, but due to shrink the water level
elements delay the decrease. When shrink subsides the feedwater regulating
valve will close returning the water level to normal. When steam flow and feed
flow are equal and the water level is normal the system will stabilize at the
new demand.
c. Main Feed Pump Control System - Feed
pressure increases above setpoint causing the main feed pump to decrease in
speed until the feed pressure is reestablished at setpoint.
d. Main Feed Pump Recirculation Control
System - Assuming the recirc valve is shut; when flow through the main feed
pump decreases to 60 GPM, the recirc valve will open to prevent the main feed
pump from overheating.
J. Effects on Plant Operations and
Capabilities During Various Boiler Evolutions
1. Blowing Tubes - This normally has no
effect on operations, however boiler load can possibly be limited by desuperheated
steam usage. NSTM recommends a steaming
rate of at least 50% to effectively remove debris clear of the stack. Windbox casing pressure is raised 2 inches
of water by using the fuel/air ratio relay.
2. Surface Blowing - The bridge should
not maneuver the ship or order any speed changes during this evolutions the
feedwater is being controlled in remote manual at a higher level than normal.
K. Boiler Flexibility Test - This is
a test conducted on the automatic boiler control system to evaluate the performance of the
system. Conducted on one boiler at a
time. A 70 % ramp change, as determined
by fuel oil header pressure, is imposed on the boiler being tested. These ramps are conducted for 45 seconds. The
controls must respond by returning steam drum
pressure to setpoint plus or minus 5 PSI, water level to normal plus or minus
1", forced draft blower speeds
must be within 300 RPMs of each other. There must be no smoke at any time during the test. The system must meet these
requirements within 4 minutes of the
beginning of the ramp load change with an additional 2 minutes settling time at the end to ensure the system is stable.
1. The ramp load change is done on the increase
first and then on a decrease (up ramp and then a down ramp).
2. Prior to conducting a flexibility test the
ABC technician conducts a series of On-Line Verification (OLV) Checks. These
let the technician know if the ABC system will satisfactorily meet flexibility
test requirements. All ships do not have the OLV package installed onboard
which makes testing difficult at times.
3. The EOOW must have control of the shaft
during the test. The bridge should not try to maintain course and speed as
these can interfere with the test.
4. Flexibility test are conducted semi-annually
per PMS. Also they are also conducted for INSURV, PEB, ETG and after each
overhaul period.
|
|
Figure 1
|
|
Figure 2
|
|
Figure 3
|
|
Figure 4