INFORMATION SHEET

 

BOILER FLEXIBILITY TEST

Information Sheet Number 62S-108

 

INTRODUCTION

 

            The purpose of the boiler flexibility test is to ensure that shipboard boiler automatic combustion and feedwater control systems are correctly installed and adjusted to maintain boiler steam pressure, water level, and combustion conditions within specifications during steady state and transient conditions and to obtain reference data suitable for verifying continued satisfactory performance of boiler automatic combustion and feedwater systems.

 

INFORMATION


 

A.                 Applicability and Frequency

 

1.  The boiler flexibility test will apply to all ships powered by steam boilers equipped with automatic combustion and feedwater control systems, provided that fuel oil burners are of the wide range (mechanical,  steam atomization) type.  Boiler flexibility test results shall be:

 

a.  Entered in the engineering log.

 

b.  Entered on data sheet 11 of the OLV manual.

 

c.  Data sheets must be retained onboard at least one year.

 

d.  Entered on Boiler Water Chemistry Work sheet Log.

 

e.  Entered on PMS card.

 

2.  A complete set of readings shall be taken and recorded for all  propulsion equipment on line at the start of and completion of each ramp load change.  Though not recorded on the data sheets, this information is required for diagnostic evaluation of deficiencies.

 

3.  Ramp load change of 70 percent of full power in 45 seconds, within a range of 15‑25% low end and 85‑95% high end.

 

4.  Flexibility tests shall be accomplished with the boiler control systems in the full automatic mode.

 

5.  Pre-test Conditions

 

a.  Verify that all interacting systems such as forced draft blowers and governors, main feed pumps and associated controls, auxiliary exhaust system, fuel oil pump pressure regulators, and fuel oil burners are operating properly.

 

b.  There shall be sufficient fireroom auxiliary equipment on the line to support the 100 percent single boiler steaming rate.

 

c.  The test boiler shall have all burners in service using normal underway sprayer plates.

 

d.  All automatic controls in the machinery space (except for the idle boiler combustion control system) shall be in the automatic mode.

 

e.  Prior to conducting boiler flexibility test, it shall be determined that forced draft blowers are parallel to within 300 RPM under steady state steaming conditions at both upper and lower boiler load conditions.

 

f.  Visual smoke indicators shall be in good working conditions and free of soot or dirt on optical surfaces.

 

6.  Verify that the calibration of the following gages that are to be used in the test are current:

 

a.  Boiler steam drum pressure

 

b.  Burner fuel oil pressure

 

c.  HP Turbine first stage steam pressure

 

7.  Boiler water gages shall be provided with scales or otherwise marked with numerals at half inch intervals from the specified normal water level from minus 8 to plus 10.

 

8.  In the event that both initial and final flexibility test loads cannot be attained with one boiler in operation, a second boiler may placed on-line.  When two boiler are in operation in the machinery space, the boiler to be tested shall be in full automatic control and the other boiler shall be under remote manual combustion control. 

 

This boiler shall be adjusted to the firing rate necessary to maintain the steaming rate required to establish the desired initial steaming rate on the boiler to be tested;  this firing rate should then be maintained through the flexibility test which follows.

 

B.                 Testing Procedures

 

1.  Determination of boiler load.

 

2.  Divide the design boiler full power fuel oil rate by the total number of burners per boiler (Figure 1).

 

 

                                            CE - WALLSEND FUEL OIL BURNER

                    STEAM ATOMIZATION - DIESEL FUEL MARINE (MIL-F-16684)

 

 

CONDITION

FULL POWER

Rating, % F.P. (oil rate)

120

Total Oil Flow, lb/hr/boiler

13,180

No. Burners in Operation

4

Sprayer Plate Size

5X 80555589

Oil Flow per Burner, lb/hr

2,740

Fuel Oil Pressure, psi

290

Atomizing Stm. Pressure, psi

150 ±15

Press. Drop Across Register, in. H2O

21

 

 

                                                                        Figure 1

 

 

1.  Multiply the oil rate determined in step (a) by lower limit of percent boiler full power to be achieved during the boiler flexibility test (15 to 25 percent)  to obtain a per-burner fuel oil rate for this lower unit.

 

2.  Using the sprayer plate capacity curve for the sprayer plates in service read the values of fuel oil rate calculated in step (b) and obtain the corresponding fuel oil burner pressure from the other axis of the curve.  This fuel oil pressure will provide the required lower limit oil rate with all burners in service (Figure 2).

 

1                                       Figure 2


 

 

 

 

 

 

 

 

 

 

3.  To obtain a per-burner fuel oil rate for the upper limit of percent boiler full power to be achieved during the boiler flexibility test (85 to 95 percent), multiply the value of per-burner oil rate determination in step (a) by the upper limit percent of boiler full power.

 

4.  Enter the sprayer plate capacity curve at the fuel oil rate calculated in step (d) and obtain the corresponding fuel oil  burner pressure.  This fuel oil pressure will provide the required upper limit oil rate with all burners in service.

 

B.                 Throttle Manipulation

 

1.  Manually adjust the main turbine throttle to the position required to obtain the steady state lower limit fuel oil pressure.  This throttle position will establish the initial load for conducting the boiler flexibility test.  Mark the throttle at this position. When conditions have stabilized the initial load, slowly open the main turbine throttle to the position required to obtain the upper limit burner fuel oil pressure.  This throttle position will establish the final load for conducting boiler flexibility test. Mark the throttle at this position.  The number of turns of the throttle required to change the load from the initial value to the final value should be recorded.

 

2.  Drill the throttleman in moving the throttle to produce a linear change in steam pressure between the upper and lower throttle position limits in the prescribed time interval of 45 seconds.  The rate of change of throttle position must be regulated by the throttle operator to maintain a smooth, continuous linear change of turbine steam pressure as indicated by the specified gage.  It is important to note that linear changes in steam pressure may require variations in the rate of change of throttle opening and closing.

 

C.                 Conducting the Boiler Flexibility Test

 

1.  When steady-state conditions have been attained, the throttle should be manipulated in a manner to impose the boiler flexibility test load change on the boiler being tested.  During the period of this test, the boiler plant in the other machinery space(s) shall be operated at a steady state steaming condition.  The ship shall maintain course throughout the entire procedure.

 

D.                 Guidelines for interpretation of boiler flexibility test results

 

1.  The two basic purposes for conducting a boiler flexibility test are as follows.

 

2.  To ensure that shipboard boiler automatic combustion and feedwater control systems are correctly installed and adjusted to maintain boiler steam pressure, water level and combustion within specification requirements during both steady-state and transient conditions.

 

3.  To obtain reference data suitable for verifying continuous satisfactory performance of boiler automatic combustion and feedwater control systems.

 

4.  The test requirements will reflect the following consideration of the ability of the boiler, supporting machinery and control systems to maintain boiler steam pressure, water level and combustion conditions during both steady-state and transient conditions.

 

E.                  General information

 

1.  Flexibility test results must be evaluated prudently.  Failure to meet one or more of the test criteria does not necessarily mean that the affected boiler cannot be steamed safely in the full automatic mode.  For example, if the transient boiler water level deviation exceeded the allowable limit by half an inch, this may indicate that the boiler control system is not functioning properly. However, correction of the problem could be delayed.  On the other hand, if during the transient test, boiler water level barely stayed in the gage glass, this would indicate a condition that could lead to serious boiler damage and should be corrected as soon as possible.

 

2.  When evaluating the results of a boiler flexibility test, past test results may be use to determine if any significant degradation of system performance has occurred.  To be used in this manner, numerical values of the test parameters must be recorded rather than simply noting whether the test results were satisfactory or unsatisfactory.

 

3.  Any outside factors that significantly influence test results should be noted.  Significant influencing factors in this context are defined as any factors that change test results from satisfactory to unsatisfactory. 

            Two examples of outside factors that can significantly effect test results are rolling of the ship and any problems that prevent generating the smooth ramp load change.  When outside factors significantly affect test results, the test should be rerun following correction of the problem.

 

F.                  Test Requirements

 

1.  Main boilers and their associated control systems shall meet the following performance requirements during a 70 percent "ramp" load change of boiler full power in 45 seconds, which is a range of 15 to 95 percent of boiler full power:

 

2.  To obtain reference data suitable for verifying continuous satisfactory performance of boiler automatic combustion and feedwater control system.

 

G.                 Performance Criteria

 

1.  Level one boiler flexibility test must meet all of the following:

 

a.  Steady state stability

 

b.  controlled system pressure - Within +/‑5 psig of set point

 

c.  water level - Within +/‑1" of normal water level

 

d.  forced draft blower - parallel within 300 RPM

 

e.  Transient Response (max. allowable deviation)

 

f.  Steam pressure - Minus 8% of steam drum pressure on the increase and plus 3% of steam drum pressure on the decrease

 

g.  Water level - Within +/- 4" from the normal water level

 

h.  Stack Condition - Smokeless

 

i.  Stabilize within four minutes - From the start of the load change, and remain stable for an additional two minutes.

 

j.  For levels 2, 3, and 4, criteria refer to Figures 3 and 4.

 

 


 

TEST PARAMETERS

BOILER FLEX TEST LEVEL

STEADY STATE STABILITY

I

II

III

IV

Steam Pressure Deviation from Setpoint (PSIG)

±5

±10

±10

±15

Water Level Deviation from Normal (INCHES)

±1

±1½

±2

±2½

FDB Parallelism - If Applicable (RPM)

300

400

500

600

TRANSIENT RESPONSE

 

 

 

 

Steam Drum Pressure Deviation (%)

(See Below)

Drum Controlled from set-point pressure

UP

-8%

-9%

-10%

-12%

 

 

DOWN

+3%**

See Note 1

See Note 2

See Note 5

 

Superhtr or common Hdr from starting Drum Press

UP

-6%

-7%

-8%

-10%

 

 

DOWN

+2%

See Note 3

See Note 4

See Note 5

Water Level Deviation - See Table 2 for applicable variation.

(INCHES)

±4

±4

+5, -4_

+6, -5_

+7, -6

 

±5

±5

+5_, -5_

+6_, -5_

+7, -6

 

±6

±6

+6_, -6

+6_, -6

+7, -6

 

+6, -5

+6, -5

+6_, -5_

+6_, -5_

+7, -6

Settling Time - See definition enclosed.

4 min.

4.5 min

5 min

6 min

Stack Condition

(Black or White smoke)

Clear

Lt. Haze

Haze*

Dark*

 

NOTES:     SVS - Superheater Safety Valve Setting (See Boiler Tech. Man.)

                  1.  SVS X 0.33 - (0.31 X Stm Drum Setpoint)

                  2.  SVS X 0.67 - (0.66 X Stm Drum Setpoint)

                  3.  SVS X 0.33 - (0.317 X Starting Drum Pressure)

                  4.  SVS X 0.67 - (0.633 X Starting Drum Pressure)

                  5.  SVS must not lift to comply with level IV requirements.

            *  Revised from previous acceptance criterion.

            **  +4% for LHA - 1 and LHD - 1 classes.

 

                                                                        Figure 3


 

LEVEL I WATER LIMIT VARIATIONS

+5, -5

+6, -6

CV - 62 - 64, 67

AOE - 1 - 4, 6

AE - 22 - 23, 27 - 29, 32-35

LHA - 1 - 5

AFS - 4

LHD - 1 CLASS

AO - 177 - 180, 186

 

LPH - 9 - 12

 

 

NOTE:

            1.  Level I requirements for all other ships are +4, -4 inches.

 

                                                                        Figure 4