INFORMATION
SHEET
FEEDWATER
CONTROL SYSTEMS
Information
Sheet Number 62S-105
INTRODUCTION
The Automatic feedwater control
systems maintain boiler water level and delivery pressure at a desired
setpoint. This objective is
accomplished by manipulating a feed control valve and the speed of the main
feed pump. This lesson will provide the
basic control functions and component interrelationships understanding.
REFERENCES
(a) Automatic Combustion and Feedwater Control
Systems NAVSEA 0951‑036‑9010
(b)
Steam Plant Controls NSTM Chapter 225
(c)
Boiler Technician 3 and 2
NAVEDTRA 10535 G, Chapter 6
INFORMATION
A.
Feedwater
Control Systems
1.
Each boiler is installed with a three element feed system (Figure
1). It is an automatic system which
controls feed flow to each boiler. The
three element feedwater control systems position the feedwater control valves
to each boiler, maintaining normal water level in the steam drums. Steady water level indicates that a balance
exists between the water flow to the boiler and the steam removed.
2.
The feedwater control system is a three‑element type, designed to
monitor changes in the primary sensing elements: steam flow, feed flow and drum
level. With changes in boiler load
(steam flow) steam and feed flow become unbalanced and water level consequently
deviates from the normal position. In
such an event, the system changes water flow in the proper direction and to the
extent necessary to restore the balance between steam flow and feed flow and
return the water level to normal.
3.
Three elements are measured by the system:
a.
Steam flow is considered the demand signal.
b.
Feed flow is considered the feedback signal.
c.
Drum level is considered the supervisory signal.
|
Figure 1 |
1.
Components:
a.
Steam and feed flow transmitters are identical in construction. These transmitters incorporate a
differential pressure unit (DPU) which measures the pressure drop across an orifice
with a mechanical square root extractor.
The transmitter generates a pneumatic output signal that is proportional
to flow.
b.
Drum level transmitters compare the weight of constant and variable legs
of water that result in a differential pressure. A continuous output signal is provided that is proportional to
drum level. The output of the drum
level transmitter will be 30 psig when the steam drum water level is normal.
c.
The steam flow/feed flow relay for a Hagan system consists of a 4
chamber totalizer with a 30 psig spring attached to chamber 3. The purpose of this relay is to subtract the
feed flow signal from the steam flow signal.
The spring adds 30 psig to the result.
When the inputs of the steam flow and feed flow transmitters are equal
the output of the relay will be 30 psig.
d.
Feedwater flow controllers in a Hagan system are 4 chamber ratio
totalizers which function as proportional‑plus‑reset
controller. Reset action is
accomplished by feeding the output of the
automatic‑manual transfer station back to chamber 4 through a needle valve and volume tank. The purpose of this controller is to compare
demand signal to supervisory signal and develop an output to return drum level
to normal. Shrink and swell are
compensated for in the operation of the feedflow controller. On an increase in boiler demand swell
offsets the increased output of the steam flow/feed flow relay by causing an
increase in the drum level transmitter output.
These inputs received by the feedflow controller are both increasing,
thus the output remains the same to the automatic/manual control station. The same is true for shrink with the
exception that both inputs decrease.
e.
Feedwater automatic/manual transfer stations allow the operator two
modes of control: automatic or
manual. Automatic mode is used for
routine steaming operations and manual mode for plant startup, securing, and
casualty control.
f.
Feedwater control valve and positioner are diaphragm control valves
which are normally operated by changes in pressure to the control air
connection from the positioner. A handwheel
is fitted on the top of the valve to permit manual closing during maintenance
and local manual operation. The
feedwater control valve positioner is used to physically position the feedwater
control valve. A mechanical linkage on
the positioner connected to the valve stem provides feedback of the actual
valve stem movement.
When
the controller output calls for the valve stem to change position, the
positioner acts as a pneumatic relay, through a separate air supply, to
increase or decrease the pressure to the valve actuator and change the position
of the stem as required by the controller output signal.
2.
System operation (Increase in boiler demand):
a.
Increase steam flow sensed by steam flow transmitter
b.
Steam flow transmitter output increases
c.
Drum level transmitter output increases due to swell
d.
Feed flow controller unchanged due to increased inputs from steam flow
transmitter and drum level transmitter balance
e.
As swell decreases, feed flow controller output increases
f.
Feedwater automatic/manual transfer station passes signal through in
automatic
g.
Feedwater control valve positioner output decreases, to position control
valve stem in correct position to increase feed flow
h.
Feed flow transmitter senses increased flow and increases output signal
i.
Steam flow and feed flow transmitters balance
j.
Steam flow/feed flow relay returns to 30 psig
k.
Drum level returns to normal
l.
Drum level transmitter at 30 psig
m.
Feed flow controller balanced at new increased value
n.
Decrease in boiler demand is the opposite of an increase in demand.
3.
Main feed pump constant pressure control system (Figure 2)
|
Figure 2 |
a.
The main feed pump constant pressure control system ensures the main
feed pump maintains a constant discharge pressure.
b.
The control system consists of a hydraulic system which uses lube oil as
a control medium, and a pneumatic system which utilizes air as a control
medium. A pneumatic bellows, which
actuates the turbine control system in response to the pneumatic signal from
the feedwater system, is mounted on each turbine. The pneumatic control components for the main feed pumps are
located in a control panel in each fireroom, with automatic/manual stations on
the combustion control console.
c.
Components:
(1)
Feedwater header pressure controller senses feedwater header pressure
and exerts a force on an installed beam.
The set point spring, which opposes the force exerted by the high
pressure bellows is adjusted to balance the regulated feedwater header pressure
to setpoint. The output of the feed
header pressure transmitter is proportional to the pressure sensed.
(2)
Signal range modifier acts as a system pressure interpreter. For example, the Hagan system pressure range
is from 5-60 psi representing 100 percent range. The main feed pump governor has a working range of 3-47.5 psi
representing 100 percent. The range
modifier in this application establishes compatibility between the normal 5‑60
psi range and that required by the feed pump governor.
d.
Main feed pump automatic/manual transfer station gives the operator two
modes of control: automatic or
manual. One is installed for each main
feed pump. Output goes to the bellows on the main feed pump turbine control operator
(governor). It is important to note
that the main feed pump governor will be reverse acting to the incoming
signal. On an increase of demand the
increased demand signal will be reversed to a lower signal to the pump controls
allowing the pump to turn faster. The
opposite occurs on a decrease in demand.
4.
System operation (increase demand):
a.
Feed header pressure decreases
b.
Feed header pressure controller output decreases
c.
Signal range modifier decrease input gives decrease output
d.
Automatic/manual transfer station passes signal through in automatic
e.
Decrease input to main feed pump causing increase in RPM
f.
Increased RPM causes rise in feed header pressure
g.
Decrease in boiler demand are opposite of increase in demand.
NOTE: There are a number of ships that do not
utilize the Hagan feed header pressure
systems. These ships use a Leslie
constant pressure regulator that simply
monitors header pressure and alters the position of the steam admission valve to the main feed pump directly
via a governor assembly.
B.
System
Deficiencies:
1.
The control air must be free of moisture and particulate matter. The smallest amount of moisture or
particulate matter in a control system will foul small orifices and cause a
malfunction of the system. If a component in the system malfunctions, securing
the plant to repair it may not be required.
In many cases the control system may be placed in remote or local
manual, the component isolated and then replaced with a bulkhead spare. A complete knowledge of the control system's
functions is necessary to make such critical decisions. It must be understood that when a control
system is in remote or local manual the plant load must be increased or
decreased slowly as an operator is not as responsive as the control system
would be in automatic.
2.
Other problems are: improper PMS being preformed, leaking air lines or
fittings, component covers not installed, loose set screws on regulators, and
components not mounted correctly (missing bolts or not tight).